Collector OPC UA

Prev Next

The purpose of this article is to be a reference for the OPC UA collector part of the full Data Collection Module documentation

The OPC UA collector is used to collect samples (data points) from any OPC UA enabled equipment, either by using a single collector or multiple collectors if collecting from multiple different devices.

Config main

The Config main (array of objects, mandatory) contain the following fields:

Function Type Importance Description
ConfigName string mandatory Unique name for this configuration file. Follows the rules for names.
ConfigDescription string optional text describing this configuration.
CheckpointInterval integer == 0 or >= 60 optional The interval with which all data from the internal datasample cache is saved to disk. The more unstable power that the SiteManager has, the more often data should be saved. Saving it often, however, will also cost performance and wear on the storage medium. A value of 0 means that it never checkpoints, otherwise it is an interval in seconds between saves. If not specified the value 900 (15 * 60sec = 15 minutes) is used.
AlarmsSaved integer >= 4 optional The number of alarms saved in the Store and Forward database. If this values is not specified, it will default to 32.
WaitForNTP boolean optional Synchronize DCM data collection with NTP time. If this parameter is true, all DCM collectors will not begin collecting data until NTP is enabled and configured and NTP has synchronized date/time. If not specified, the value is true.

Since the JSON format itself doesn't define a comment notation, DCM accepts the field name comment with any type of value in any section.

Example of comment:

"Comment": "Example of a comment for use in any section."

OPC UA Collector main

The Collectors (array of objects, mandatory) list of elements contains the following fields:

Function Type Importance Description
CollectorName string mandatory Unique name (within this confguration file) of a device to collect data from. (This is the name used in the agent configuration.) Follows the normal rules for names.
CollectorDescription string optional Description of this collector. (For your use, no system function)
CollectorIPAddr string optional Default IP address (or DNS name) for the device to be polled. The agent Target IP address will take precedence over this.
CollectorPortno integer > 0 and < 65535 optional Default port number for the device to be polled. The agent Target Port number will take precedence over this. If neither CollectorPortno nor agent Target Port Number is specified, the appropriate port will be used, depending on the Protocol parameter value.
Alias string optional This is the CollectorName of another collector, from which all the parameters (except CollectorName , CollectorDescription , CollectorIPAddr and CollectorPortno ) are copied. An alias cannot refer to another alias.
Protocol string-enum mandatory The protocol used to collect data. Possible values are: OPC-UA/TCP, Modbus/TCP, Http/GET and Simulator.
ConnectRetryMin integer > 0 mandatory The minimum number of seconds before trying to re-establish a connection to the device being sampled. An exponential backoff algorithm is used to retry connection establishment, starting after ConnectRetryMin and increasing to ConnectRetryMax.
ConnectRetryMax integer > 0 mandatory The maximum number of seconds before trying to re-establish a connection to the device being sampled.
OPCUAAccess Object optional Collection of parameters needed to access a given OPC-UA/TCP server.
SamplePoints Array of objects mandatory List of samples to be collected, possibly aggregated and Store and Forward database.

OPCUAAccess

Note:

The Security mode is an EXPERIMENTAL new feature and all security-related configuration is subject to change.

Important:

OPCUAUsername and OPCUAPassword are deprecated and will probably be removed in a future release.

The OPCUAAccess object contains the following elements:

Function Type Importance Description
OPCUASecurityMode string-enum optional The security mode for the communication channel between DCM (OPC-UA client) and the OPC-UA server. Possible values are: none, sign and signencrypt. Unless specified otherwise, none is set as default.
OPCUASecurityPolicy string maybe-optional The security policy is mandatory, when the OPCUASecurityMode is sign or signencrypt. Possible values are: none, Basic128Rsa15, Basic256, Basic256Sha256 and Aes128_Sha256_RsaOaep. If not specified, none will be used.
OPCUACertificate string optional The name of the certificate used for authentication during the collection of data if the OPCUASecurityMode is sign or signencrypt. If not specified, the name opcua-cert-CollectorName will be used. If such a certificate does not exist in the certificate store, it will be created.
OPCUAPrivateKey string optional The name of the private key to use for encryption during collecting of data if the OPCUASecurityMode is sign or signencrypt. If not specified, the name opcua-pkey-CollectorName will be used. If such a private key does not exist in the certificate store, it will be created.
OPCUAServerCertificates array of strings optional The name of the certificates imported from the OPC-UA server(s), that the collector retrieves data from. If no server is specified, any server will be accepted as being valid. If specified as an empty array, then all certificates of the OPC-UA Server certificate type will be used.
OPCUAUserTokenType string-enum mandatory The user authentication methods used when collecting data. Possible values are: anonymous, username, certificate and issuedtoken.
OPCUAUserTokenName string maybe-optional Mandatory if OPCUAUserTokenType is username, certificate or issuedtoken. The field refers to an entry in/name from the certificate store, which should contain the following: For username a file with 2 lines of text - the username and the password. For certificate an X.509 certificate. For issuedtoken a BASE64 encoded text file.
OPCUAUsername string maybe-optional The username to use for the OPC-UA session. To use OPCUAUsername it is a requirement that OPCUASecurityPolicy and OPCUASecurityMode is set to something other than none. Note that this parameter is deprecated and will probably be removed in a future release. Instead, we recommend using OPCUAUserTokenName as it is more flexible and secure.
OPCUAPassword string maybe-optional The password to use for the OPC-UA session. To use OPCUAPassword it is a requirement that OPCUASecurityPolicy and OPCUASecurityMode is set to something other than none. Note that this parameter is deprecated and will probably be removed in a future release. Instead, we recommend using OPCUAUserTokenName as it is more flexible and secure.
OPCUAPath string optional Additional path component to the URL used for connecting to the OPC-UA server.
OPCUABrowseRootIds array of OPCUABrowseRootId optional The OPC-UA node id to start browsing for relative browse paths from.
OPCUATimeStampPolicy string-enum mandatory The timestamp to mark collected data with. Possible values are: source, server and dcm. If the polled OPC-UA server does not support the requested timestamp, DCM will fall back from Source->Server->DCM. This field also serves as the default value for the optional field OPCUATimeStampPolicy in sample OPCUAObject.
OPCUATimeout integer > 0 optional Timeout (in millisecond) for OPC-UA query requests. If not present the value 5000 is used.

Samplepoint

The SamplePoints objects contains the following elements:

Function Type Importance Description
SampleName string mandatory Name of this sampled value (sometimes called a tagname). Follows the normal rules for names.
SampleDescription string optional Is a text description of this sample value.
SampleUnit string optional Is a description of the unit measurement for this sample.
SampleGroup string optional Designates (in some datasrvs) that all samplepoints in that group should be handled (displayed) together. The DCM system itself places no meaning on this group affiliation.
SamplesSaved integer > 0 optional Is the number of values collected that is saved in the Store and Forward database even after the values have been sent to all dataservers. When 0 is specified, the value can be used in aggregators, but nothing is sent via dataservers to cloud system. If left unspecified, values are only saved in the Store and Forward database until they have been delivered to all dataservers.
OnlySaveOnChanged bool optional Specifies whether new sample values should be saved to the Store and Forward database only if the values have changed since last sample. Defaults false.
ChangeLimit Integer/Double optional Only used if OnlySaveOnChanged is true. This describes a limit for what "changed" means. If a new sample value is this amount less or more than the previous sample value, it is considered the "same" value. This is a simple hysteresis to filter out inaccurate (jitter) measurements.
SampleDataType string-enum mandatory The type of data collected. The possible values are: bool (1 bit), sbyte (8 bit signed), byte (8 bit unsigned), int16 (16 bit signed), uint16 (16 bit unsigned), int32 (32 signed), uint32 (32 bit unsigned), int64 (64 bit signed), uint64 (64 bit unsigned), float (32 bit), double (64 bit), string (variable text up to 24575 bytes. Includes terminating NUL), data (variable data up to 24575 bytes). This collector might not support all SampleDataTypes.
SampleMaxVDataSize integer > 0 and <= 24575 optional Is the max size of variable data enforced for this sample. This is only relevant for SampleDataType string and data. Defaults to 1024.
SampleLowerLimit integer/double optional The lower limit for the collected data. If the collected data value is less than SampleLowerLimit it is evaluated in accordance with SampleLimitDiscard and SampleLimitAlarm.
SampleUpperLimit integer/double optional The upper limit for the collected data. If the collected data value is more than SampleUpperLimit it is evaluated in accordance with SampleLimitDiscard and SampleLimitAlarm.
SampleLimitDiscard bool maybe-optional Specify whether a sample limit violation results in the sample value being discarded. Mandatory if either SampleLowerLimit or SampleUpperLimit is present.
SampleLimitAlarm bool maybe-optional Specify whether a sample limit violation generates an alarm. Mandatory if either SampleLowerLimit or SampleUpperLimit is present.
OPCUAObject Object maybe-optional Description of how to address a specific OPC-UA object, when values are collected from it. Mandatory if the protocol type is OPC-UA/TCP.

OPCUABrowseRootId

The OPCUABrowseRootId object contains the following fields:

Function Type Importance Description
BrowseRootID integer >= 0 mandatory Is a unique ID for this entry. (Used by the OPCUAObject entries).
NodeIdNameSpaceIndex integer >= 0 and < 65535 maybe-optional This is the OPC-UA NodeID type. (ID type of the tag) The possible values are: numeric, string, guid or bytestring.
NodeIdType string-enum mandatory This is the OPC-UA NodeID type. The possible values are: numeric, string, guid, bytestring or browsename.
NodeIdNumeric integer >= 0 and < 4294967295 maybe-optional This is OPC-UA NodeID numeric value. Only mandatory if the value of NodeIdType is numeric.
NodeIdString string maybe-optional This is OPC-UA NodeID string value. Only mandatory if the value of NodeIdType is string or browsename. For browsename it is the node browsename to be searched for, starting from OPCUABrowseRootId and forwards in the tree.
NodeIdGuid string maybe-optional This is OPC-UA NodeID GUID value. Only mandatory if the value of NodeIdType is guid. The format is hex-digits with hyphens enclosed in curly brackets: {XXXXXXXX-XXXX-XXXX-XXXX-XXXXXXXXXXXX} (38 characters).
NodeIdByteString string maybe-optional This is OPC-UA NodeID byte string value. Only mandatory if the value of NodeIdType is bytestring. The format is hex-digits. Must not be an empty string and must contain a even number of hex digits.
NodeIdBrowsePath array of strings maybe-optional This is OPC-UA NodeID browse path. Only mandatory if the value of NodeIdType is browsename. This browsepath is relative to the official OPC-UA root folder namespaceindex 0 (numeric: 84). Each string in the array follows the OPC-10000-3 section C.2.3 syntax: [<namespaceindex>:]<browsename> where the <namespaceindex> can be omitted if namespaceindex is 0.

OPCUAObject

The OPCUAObject object contains the following fields:

Function Type Importance Description
NodeIdNameSpaceIndex integer >= 0 and < 6553 maybe-optional This is the OPC-UA namespace index. When NodeIdType is browsename, this index is not used and is therefore optional.
NodeIdType string-enum mandatory This is the OPC-UA NodeID type. The possible values are: numeric, string, guid, bytestring or browsename.
NodeIdNumeric integer maybe-optional This is OPC-UA NodeID numeric value. Only mandatory if the value of NodeIdType is numeric.
NodeIdString string maybe-optional This is OPC-UA NodeID string value. Only mandatory if the value of NodeIdType is string.
NodeIdGuid string maybe-optional This is OPC-UA NodeID GUID value. Only mandatory if the value of NodeIdType is guid. The format is hex-digits with hyphens enclosed in curly brackets: {XXXXXXXX-XXXX-XXXX-XXXX-XXXXXXXXXXXX} (38 characters).
BrowseRootREF integer >= 0 and integer >= 0 maybe-optional This is a reference to the OPCUABrowseRootIds element with the same value of it's field OPCUABrowseRootId. This field is only used, when the NodeIdType is browsename.
NodeIdBrowsePath array of strings maybe-optional This is OPC-UA NodeID browse path. Only mandatory if the value of NodeIdType is browsename. This browsepath is relative to the browseroot specified with the BrowseRootREF value. If the BrowseRootREF is left unspecified, it is an absolute browsepath starting from the Root node. Each string in the array follows the OPC-10000-3 section C.2.3 syntax: [<namespaceindex>:]<browsename> where the <namespaceindex> can be omitted if namespaceindex is 0.
NodeIdByteString string maybe-optional This is OPC-UA NodeID byte string value. Only mandatory if the value of NodeIdType is bytestring. The format is hex-digits. Must not be an empty string and must contain an even number of hex digits.
OPCUASampleInterval integer >= 0 mandatory The number of seconds between each sample of this OPC-UA object. If the interval is 0, only event-driven polling is used.
OPCUATimeStampPolicy string-enum optional The timestamp to mark this sample data with. Possible values are: source, server or dcm. If this field is not present the OPCUATimeStampPolicy filed from the OPCUAAccess object - that this sample belongs to - will be used instead.

Example configuration

Example of collector with OPCUAAccess, Samplepoints and OPCUAObject objects:

{
 "CollectorName": "OmronOPCUA",
 "CollectorDescription": "Example Omron NX1 with OPC-UA Server",
 "Protocol": "OPC-UA/TCP",
 "ConnectRetryMin": 2,
 "ConnectRetryMax": 240,
 "OPCUAAccess": {
  "OPCUASecurityPolicy": "none",
  "OPCUAUserTokenType": "anonynmous",
  "OPCUATimeStampPolicy": "dcm"
  },
 "SamplePoints": [
 {
 "SampleName": "Temp1",
 "SampleDescription": "B1 Potmeter",
 "SamplesSaved": 1000,
 "SampleDataType": "int16",
 "SampleLimitDiscard": true,
 "SampleUpperLimit": 8100,
 "SampleLowerLimit": 0,
 "SampleLimitAlarm": false,
 "OPCUAObject": {
  "NodeIdNameSpaceIndex": 4,
  "NodeIdType": "string",
  "NodeIdString": "Analog1",
  "OPCUASampleInterval": 4
  }
  }
 ]
}

Example of collector for OPC UA server on Siemens PLC

{
  "CollectorDescription": "Example with Siemens PLC w/OPC-UA Server",
  "CollectorName": "Test2OPCUA",
  "ConnectRetryMax": 240,
  "ConnectRetryMin": 10,
  "OPCUAAccess": {
   "OPCUASecurityPolicy": "none",
   "OPCUATimeStampPolicy": "dcm",
   "OPCUAUserTokenType": "anonynmous"
   },
  "Protocol": "OPC-UA/TCP",
  "SamplePoints": [
 {
  "OPCUAObject": {
  "NodeIdNameSpaceIndex": 3,
  "NodeIdString": "\"DB_MRUSim\".\"Out\"",
  "NodeIdType": "string",
  "OPCUASampleInterval": 1
 },
  "SampleDataType": "double",
  "SampleDescription": "AHC curve",
  "SampleName": "AHC",
  "SamplesSaved": 10
  }
 ]
}