--- title: "Controlling remote access to SiteManager via IO port" slug: "controlling-remote-access-to-sitemanager-via-io-port" tags: ["IO port", "Remote access"] updated: 2026-06-09T14:33:54Z published: 2026-06-09T14:33:54Z canonical: "kb.secomea.com/controlling-remote-access-to-sitemanager-via-io-port" stale: true --- > ## Documentation Index > Fetch the complete documentation index at: https://kb.secomea.com/llms.txt > Use this file to discover all available pages before exploring further. # Controlling remote access to SiteManager via IO port ## Overriding remote access to SiteManager via IN 1 port Remote access to a SiteManager and its associated connections can be controlled by a physical switch or relay connected to the **IN 1** port. This allows the final decision to enable or disable remote access to be made locally at the hardware level, independent of software configuration. ### How the IN 1 port works The **IN 1** port is designed to be driven by a mechanical switch or relay wired between the **GND** and **Input** terminals of the SiteManager. An internal **10 kΩ pull-up resistor** keeps the input at 3.3 V when nothing is connected, so an unconnected or open port is always in the **OFF** state by default. The port uses **active-low logic**, meaning: - **Switch closed (pin grounded)** — voltage is pulled to near 0 V → input state is **ON** - **Switch open (pin floating)** — pull-up resistor holds voltage at 3.3 V → input state is **OFF** The defined voltage thresholds are: - **ON:** 0.16 V or below - **OFF:** 2.34 V or above - **Undefined:** voltages between 0.16 V and 2.34 V ### Controlling remote access Depending on how the SiteManager is configured, the IN 1 port can either enable or disable remote access when activated. Two setups are supported: - The **default setup** has remote access **enabled** by default. Activating IN 1 (closing the switch) **disables** remote access. - The **alternate setup** has remote access **disabled** by default. Activating IN 1 (closing the switch) **enables** remote access. --- ### Default setup Configure the SiteManager with the following settings: **Remote Management**: **Enabled** **Input 1 Action**: **Control Remote Management** ![Screenshot 2025-05-07 at 13.01.45.png](https://cdn.document360.io/88f49507-a7a0-4636-b297-13c4d0065310/Images/Documentation/Screenshot%202025-05-07%20at%2013.01.45%281%29.png) #### Behaviour Remote access is **enabled by default**. Closing the switch (IN 1 grounded) **disables** remote access. Opening the switch (IN 1 floating) **re-enables** it. ![Screenshot 2025-05-07 at 13.01.59.png](https://cdn.document360.io/88f49507-a7a0-4636-b297-13c4d0065310/Images/Documentation/Screenshot%202025-05-07%20at%2013.01.59.png) ![Screenshot 2025-05-07 at 13.02.14.png](https://cdn.document360.io/88f49507-a7a0-4636-b297-13c4d0065310/Images/Documentation/Screenshot%202025-05-07%20at%2013.02.14.png) --- ### Alternate setup Configure the SiteManager with the following settings: **Remote Management**: **Disabled**. **Input 1 Action**: **Control Remote Management**. ![Screenshot 2025-05-07 at 13.03.48.png](https://cdn.document360.io/88f49507-a7a0-4636-b297-13c4d0065310/Images/Documentation/Screenshot%202025-05-07%20at%2013.03.48%281%29.png) #### Behaviour Remote access is **disabled by default**. Closing the switch (IN 1 grounded) **enables** remote access. Opening the switch (IN 1 floating) **disables** it again. ![Screenshot 2025-05-07 at 13.04.02.png](https://cdn.document360.io/88f49507-a7a0-4636-b297-13c4d0065310/Images/Documentation/Screenshot%202025-05-07%20at%2013.04.02.png) ![Screenshot 2025-05-07 at 13.04.18.png](https://cdn.document360.io/88f49507-a7a0-4636-b297-13c4d0065310/Images/Documentation/Screenshot%202025-05-07%20at%2013.04.18.png)